IoT monitoring device
Field monitoring unit for electrical and process signals. This document summarizes mechanical, electrical I/O, and core hardware characteristics.
- Product
- SFPL IoT device
- Revision
- Web — summary
- I/O total
- 17 inputs
1.Physical specification
| Enclosure | ABS |
|---|---|
| Footprint (W × D X H) | 165 mm × 155 mm × 36 mm |
2.Input pin overview
The device exposes seventeen dedicated input connections, grouped by signal type for supply, mains-level AC, low-level AC (for external sensors such as CTs), and general-purpose DC analog sensing.
| Group | Count | Role |
|---|---|---|
| Power | 1 | Device supply (DC) |
| AC high | 3 | Line / phase voltage |
| AC low | 3 | CT or low-AC sensing |
| Analog DC | 9 | 0–30 V sensors |
Figures
Reference diagrams
Illustrations of the enclosure and interface layout. Use together with the pin grouping table above when planning field wiring.
3.Input supply (1 pin)
Powers the internal electronics and radio from an external DC source.
- Rating: 6–24 V DC nominal input range.
- Usage: Single supply rail for the complete device; select a source within the rated range and appropriate current capability for your installation.
4.AC high-voltage inputs (3 pins)
Isolated high-voltage channels for measuring AC potentials on distribution or branch circuits.
- Rating: Up to 300 V AC per channel (as specified for this design).
- Typical usage: Monitoring phase-to-neutral or line-to-line relationships on three-phase supplies (for example R–Y–B phase voltages) where direct mains measurement is required.
5.AC low-voltage inputs (3 pins)
Channels intended for low-amplitude AC signals from external transducers rather than direct mains connection.
- Rating: Up to 5 V AC at the input.
- Typical usage: Current transformers (CTs) or similar interfaces that deliver a proportional low voltage representing AC current on feeders or phases.
6.Analog DC inputs (9 pins)
General-purpose DC voltage inputs for industrial and building instrumentation.
- Range: 0–30 V DC measurable span (per channel specification).
- Typical usage: Pressure, level, temperature, flow, and other field devices that present a DC voltage proportional to the measured quantity.
7.Core hardware
Cellular
GSM module with 2G connectivity and integrated antenna for uplink in covered deployments.
Battery backup
Two 3.7 V cells with 1700 mAh pack capacity, to help maintain operation through short supply interruptions.