cursor
SFPL Logo
Technical specification

IoT monitoring device

Field monitoring unit for electrical and process signals. This document summarizes mechanical, electrical I/O, and core hardware characteristics.

Product
SFPL IoT device
Revision
Web — summary
I/O total
17 inputs

1.Physical specification

EnclosureABS
Footprint (W × D X H)165 mm × 155 mm × 36 mm

2.Input pin overview

The device exposes seventeen dedicated input connections, grouped by signal type for supply, mains-level AC, low-level AC (for external sensors such as CTs), and general-purpose DC analog sensing.

GroupCountRole
Power1Device supply (DC)
AC high3Line / phase voltage
AC low3CT or low-AC sensing
Analog DC90–30 V sensors

Figures

Reference diagrams

Illustrations of the enclosure and interface layout. Use together with the pin grouping table above when planning field wiring.

SFPL IoT device: enclosure and interface diagram 1
Figure 1 — Device overview / interface layout
SFPL IoT device: enclosure and connectivity diagram 2
Figure 2 — Device overview (alternate view)

3.Input supply (1 pin)

Powers the internal electronics and radio from an external DC source.

  • Rating: 6–24 V DC nominal input range.
  • Usage: Single supply rail for the complete device; select a source within the rated range and appropriate current capability for your installation.

4.AC high-voltage inputs (3 pins)

Isolated high-voltage channels for measuring AC potentials on distribution or branch circuits.

  • Rating: Up to 300 V AC per channel (as specified for this design).
  • Typical usage: Monitoring phase-to-neutral or line-to-line relationships on three-phase supplies (for example R–Y–B phase voltages) where direct mains measurement is required.

5.AC low-voltage inputs (3 pins)

Channels intended for low-amplitude AC signals from external transducers rather than direct mains connection.

  • Rating: Up to 5 V AC at the input.
  • Typical usage: Current transformers (CTs) or similar interfaces that deliver a proportional low voltage representing AC current on feeders or phases.

6.Analog DC inputs (9 pins)

General-purpose DC voltage inputs for industrial and building instrumentation.

  • Range: 0–30 V DC measurable span (per channel specification).
  • Typical usage: Pressure, level, temperature, flow, and other field devices that present a DC voltage proportional to the measured quantity.

7.Core hardware

Cellular

GSM module with 2G connectivity and integrated antenna for uplink in covered deployments.

Battery backup

Two 3.7 V cells with 1700 mAh pack capacity, to help maintain operation through short supply interruptions.